Phase Converter and VFD Sizing Calculator

A 5 hp three-phase motor is 15.2 amps on its nameplate, and that number is what people carry into the shop when they plan a single-phase service. It is the wrong number to carry. A 230 volt motor on a 240 volt single-phase supply needs roughly double that current whichever route you take, because the same power arrives through two conductors instead of three at about the same voltage, and both a rotary converter and a drive add losses and a power factor of their own. Change the voltages and the multiplier changes with them — a 460 volt motor on a 240 volt service lands between three and a half and four and a half times the nameplate figure — which is why the page works it out rather than quoting a factor.

From the nameplate. Used for the idler sizing and for context.
Line to line, from the nameplate.
The nameplate FLA at the voltage above. Not a figure from a table.
From the nameplate or the manufacturer data sheet. Lower than you expect on small motors.
The voltage of the two-wire service the shop actually has.
Total horsepower of everything else on the converter at the same moment. Enter 0 for one machine at a time.
Your own headroom. Drives are rated in continuous output amps, and matching FLA exactly leaves nothing.
The fraction of its rated output current a drive can deliver when fed single-phase, from the drive manual. A drive built for single-phase input is 1.00. Do not guess this one.
From the drive data sheet.
True power factor including harmonic distortion, from the drive manual. A drive without an input reactor or a PFC front end runs well below its displacement power factor.
From the converter manufacturer sizing sheet for the kind of load you are starting. It is not a universal figure and it moves a lot with how hard the load starts.
From the converter data, or measured.
From the converter data, or measured on the single-phase side.
What the idler draws spinning with nothing connected, measured or from the manufacturer. It runs whenever the converter is on.
Phase Converter and VFD Sizing Calculator for Shop MotorsBuildFigure

The nameplate amps are not the amps you need

A 5 hp motor with a nameplate reading 230 V, 15.2 A, power factor 0.82 is drawing 6.06 kVA and 4,965 W. That real power has to come in from somewhere, and on a single-phase service it comes in through two conductors at 240 V instead of three at 230 V. Even with a perfect converter at unity power factor that would be 4,965 divided by 240, or 20.7 A. Neither route is perfect.

Through a drive at 97 percent efficiency the input is 5,119 W, and at an input power factor of 0.65 that is 32.8 A on the single-phase line. Through a rotary converter at 92 percent efficiency and 0.9 line power factor it is 25.0 A plus 4 A of idler, which is 29.0 A. Either way it is about twice the nameplate figure, and that is the number the service has to carry.

The doubling is not a law, though, and it is worth knowing where it comes from. It falls out of the three-phase motor voltage and the single-phase supply voltage being close to each other, which is the ordinary shop pairing of a 230 V motor on a 240 V service. Put a 460 V motor on the same 240 V service and the multiplier runs 3.6 to 4.3 times, and a 575 V motor 4.4 to 5.4 times, because the same power now has to arrive at half the voltage or less. That is the point at which the conversation stops being about a converter and starts being about a transformer. The page prints the multiplier for whatever voltages you enter rather than repeating the factor of two.

The drive derating is the trap

Most general purpose drives have a three-phase input. Fed from single-phase they still work, but the input rectifier and the DC bus capacitors see a much harsher ripple current, so the manufacturer publishes a derating: the drive can only deliver some fraction of its rated output current. At 0.5, a motor needing 16.7 A of drive output requires a drive rated for 33.4 A continuous — which is a drive sold for a motor roughly twice the size.

That fraction is not a constant and it is not something to guess. Some manufacturers publish 0.5, some publish a different figure per model, some build drives specifically for single-phase input which need no derating at all, and some void the warranty on single-phase input entirely. The field defaults to 0.5 as a placeholder and the number that belongs there is the one in your drive manual.

Which one draws less is not settled

At the defaults the converter wins by 3.8 A, and that gap is fragile. It is decided almost entirely by two power factor figures. Fit an input reactor or buy a drive with an active front end and the drive input power factor climbs from 0.65 toward 0.95, taking its single-phase current to about 22 A and putting it comfortably ahead. Load the converter lightly and its idler current, which never goes away, becomes a bigger share of the total.

So the page prints which is lower for the numbers you put in and says so explicitly, rather than declaring a winner. Anybody claiming one route always draws less current than the other has not varied the power factors.

They are not the same product

The comparison above is only about amps, and amps is rarely why people choose. A drive gives one machine variable speed and a soft start, and its inrush on the single-phase side is small because the bus capacitors charge through a limiting arrangement rather than the motor pulling locked-rotor current. But the drive output feeds one motor. Machines with a control transformer, a coolant pump, a work light or a contactor coil hanging off the three-phase supply usually cannot be fed from a drive output at all without rewiring the machine.

A converter produces a three-phase bus that a whole shop can share and leaves every machine untouched, including its controls. The costs are an idler spinning all day, an idler start that is itself a substantial single-phase inrush event, and no speed control anywhere.

What is missing here

Everything about the installation. This page does not size the single-phase service, the branch circuit, the disconnect or the overcurrent device, and it does not know whether the service you have can carry 30 amps more than it does today. The currents above are running currents; starting events on both routes are separate numbers from the equipment data. The converter output leg arrangement and what it does to single-phase accessories inside a machine tool is the detail that most often turns a converter installation into a project, and it is worth settling before anything is bought.

Questions people ask

How many single-phase amps does a 5 hp three-phase motor need?

Roughly double the three-phase nameplate figure. At the defaults, a 15.2 A nameplate becomes 32.8 A through a drive at 0.65 input power factor or 29.0 A through a rotary converter with a 4 A idler, both at 240 V single-phase. The exact figure moves with the efficiency and the power factor of whichever converter you use, so put your own in.

Why does a VFD need derating on single-phase input?

Because a three-phase input rectifier fed from two wires sees a much harsher ripple current in the DC bus capacitors, and the manufacturer limits the continuous output to keep that inside what the parts can take. The fraction comes from the drive manual — it varies by model, some drives are built for single-phase input and need no derating, and some manufacturers do not permit it at all.

Is a rotary phase converter cheaper to run than a VFD?

It depends entirely on the input power factor of the drive, which is why the page computes it rather than asserting it. At the defaults the converter draws 3.8 A less, but fitting an input reactor to the drive reverses that comfortably. A converter also runs its idler all day whether a machine is cutting or not, which a drive does not.

How big an idler does a rotary converter need?

The manufacturer sizing sheet decides, and the multiple depends on how hard the load starts. The field defaults to 1.5 times the largest motor as a placeholder. A lathe coasting up under no load and a compressor starting against pressure are not the same problem, and the sizing sheet for the converter you are buying is the authority rather than any general rule.

Can I run a whole shop from one VFD?

Generally no. A drive output feeds the motor it is set up for, at a frequency it is controlling, and putting several machines on it does not work. Machines with control transformers, coolant pumps or contactor coils fed from the three-phase supply usually cannot be run from a drive output without rewiring the machine. A converter feeds a shared bus, which is the reason people still buy them.

Related